Physics-Based Solar Air-Heater Outlet-Temperature Prediction: Nested Irradiance-Blocked Evaluation and Geometry–Loss Compensation
DOI:
https://doi.org/10.46610/IJSETG.2026.v02i02.003Keywords:
Low-Reynolds-number Nusselt sensitivity, Nested irradiance-block evaluation, OpenFOAM, Parameter compensation, Reduced-order thermal modelling, Reproducibility, Solar air heaterAbstract
Accurate outlet-temperature prediction of solar air-heaters calls for valid geometric and heat-loss models. This is a retrospective computational analysis of the operating observations of 26 published data sets for a single double-channel collector at two levels of irradiation. Reciprocal irradiance-block holdouts were used to evaluate a steady energy-balance model, and the outer training blocks were the only ones used to fit the external-loss coefficient, while the inner blocks were used to validate the model in an inner leave-one-flow-group-out fashion on each outer block. The held-out RMSE of the geometry-aware model is 1.927°C, compared to 2.523°C for a top-only reference fit (23.62% lower RMSE for the geometry-aware model). The three idealized prespecified low Reynold's number Nusselt closures were tested, tested for re-selection at all levels. All three assumptions for the geometry-aware model led to a smaller RMSE (from 10.49% to 23.62% smaller, but the fitted geometric factor depended on the transfer direction and closure. This behavior promotes predictive advantage but does not help to identify whether it's internal or external heat loss. A separate simulation (1,590,202 cells) representing a smooth-duct configuration was presented only for the purpose of providing a set of numerical consistency diagnostics, and not for design and test of the source collector. Results offer an apparatus-specific evaluation framework that is repeatable and a test of the sensitivity of the inferred thermal parameters to model-form assumptions.